This product is a Multi GFP residual current circuit breaker (RCCB). It is a 4P circuit breaker with 63A In rated current, a sensitivity of 26mA with a A-SI type protection class. It protects persons against electric shock by direct contact. It also protects installations against fire risks. The tripping upon fault is indicated by a red mechanical status indicator on the front panel. The A-SI type offers enhanced immunity to electrical disturbances. This product is dedicated to original equipment manufacturers (OEM) and control panel builders in indisutrial and tertiary buildings. It is compliant with IEC/EN 61008-1 standard. The (Im/IΔm) rated breaking and making short circuit capacity is 1500A. The (Inc/IΔc) conditional rated short circuit current is 10kA. It has a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 440VAC. The Uimp rated impulse withstand voltage is 6kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 8. The product colour is light grey (RAL7035). The dimensions are (W) 72mm x (H) 81mm x (D) 60mm. The weight is 0.45kg. It has an IP20 degree of protection (as per IEC/EN 60529 standard) and becomes IP40 once in modular enclosure. The operating temperature is from -25°C to 60°C. The storage temperature is from -40°C to 70°C.
Schneider Electric M9R81463
Range Multi9 Product name Multi9 GFP Product or component type Residual current circuit breaker (RCCB) Device short name GFP Device application Distribution Poles description 4P Neutral position Left [In] rated current 63 A at 40 °C conforming to EN/IEC 61008-1 Network type AC Earth-leakage sensitivity 26 mA conforming to UL 1053
30 mA conforming to EN/IEC 61008-1Earth-leakage protection time delay Instantaneous Earth-leakage protection class Type A-SI (Super Immunised) Utilisation category AC-23A conforming to EN/IEC 61008-1 Complementary Network frequency 50/60 Hz [Ue] rated operational voltage 480Y/277 V AC 60 Hz
415 V AC 50 Hzresidual current tripping technology Voltage independent Rated breaking and making capacity Idm 1500 A conforming to EN/IEC 61008-1 Rated conditional short-circuit current Inc 10 kA 100 A gG [Ui] rated insulation voltage 440 V AC 50/60 Hz [Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 61008-1 Contact position indicator Yes Control type Toggle Local signalling ON, OFF, fault trip Mounting mode Clip-on Mounting support DIN rail 9 mm pitches 8 Height 81 mm Width 72 mm Depth 60 mm Net weight 0.45 kg Colour Grey Mechanical durability 20000 cycles Locking options description Padlocking in OFF position Connections - terminals Tunnel type terminals (top or bottom) 1…25 mm² (AWG 18...AWG 3) - flexible
Tunnel type terminals (top or bottom) 1…35 mm² (AWG 18...AWG 2) - rigid
Tunnel type terminals (top or bottom) 1…25 mm² (AWG 18...AWG 3) - flexible with ferruleWire stripping length 14 mm for top or bottom connection Tightening torque 3.5 N.m top or bottom Environment Standards EN/IEC 61008-1
UL 1053Product certifications IEC
ULIP degree of protection IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529Pollution degree 3 Electromagnetic compatibility 8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61008-1 Tropicalisation 2 conforming to IEC 60068-1 Relative humidity 95 % at 55 °C Ambient air temperature for operation -25…60 °C Ambient air temperature for storage -40…70 °C 12 Months